–51–
*
46 REPORT FORMAT
(* applies to BOTH primary and secondary numbers)
Determines which format is to be used to report to the central
station.
0 = 3+1; 4+1 ADEMCO Low Speed Standard (this is the default)
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMCO Low Speed Standard
3 = 4+2 Radionics Standard
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID Reporting (* Recommended)
8 = 3+1; 4+1 ADEMCO Low Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
*
47 SPLIT/DUAL REPORTING
Enter 0 to disable (Backup report only). This is the default.
TO PRIMARY TO SECONDARY
1 = Alarms, Restore, Others
2 = All except Test Test
3 = Alarms, Restore All
4 = All except Test All
5 = All All
*
49 PERIODIC TEST REPORT
Select the desired test report interval.
0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days. Default is 24 hrs.
Test Report Code entered in field
*
64 (or Off-Normal Test Report
*84) is sent. Must be set to "1" for fire installations.
*
50 SESCOA/RADIONICS SELECT
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats. Default is 0.
*56
ZONE ASSIGNMENT/ALARM REPORT CODES
REFER TO THE ZONE ASSIGNMENT TABLE FOR
*56
IN THE
CENTERFOLD PROGRAMMING FORM .
This is an interactive menu mode that is used to program zone
numbers, zone types, and alarm report codes. This mode can also
be used for entering Alpha descriptors for zones (however, we
recommend entering descriptors in menu mode
*82
.
Upon entering menu mode
*56
, the following is displayed:
Enter Zn Num.
(00 = Quit) 01
Zone 01 entered ↑
Zone Number (Zn): Enter the zone number that you wish to
program (or [0][0] to leave zone programming).
Zn ZT RC
01 09 10
Press [*]. A summary display will come up, showing the status of
that zone's program.
If it is programmed satisfactorily, press [#] to back up one step
and enter another zone number, if desired.
If the zone is not programmed, or you want to change it, press [*].
A prompt for Zone Type will appear.