Section 6. SYSTEM ZONES
This section provides the following information:
General information about system zones
System zone assignments
General Information
System zones may be comprised of the following:
Zones which monitor various device connections, as well as earth ground
faults
Keypad emergency zones, which may be assigned 24-hr. zone responses that
are activated
Zones which have a special purpose such as to bypass a relay, or to assign a
zone descriptor to a relay
System Zone Assignments
Zone 6: Bell Supervision – monitors the bell circuit output for open and
short circuit faults. Defaults to zone response type 19 (24-Hr.
Trouble) .
Zone 7: Keypad emergency – activated by pressing the keypad [B] key or by
simultaneously pressing the[*] and [#] keys. Keys must be held for
two seconds.
Zone 10: Earth Ground Supervisionmonitors the control's field wiring for
earth ground faults. Defaults to zone response type 19 (24-Hr.
Trouble). Supervision must be enabled (using response type 19) for
fire installations.
Zone 11: Main Dialer Supervisionmonitors the main dialer telephone
connection for line faults. Defaults to zone response type 19 (24-Hr.
Trouble).
Zone 12: Back-up Dialer Supervisionmonitors the backup dialer telephone
connection for line faults. Defaults to zone response type 19 (24-Hr.
Trouble).
Zone13: Auxiliary Relay Disable – represents the auxiliary relay for
purposes of allowing this relay to be bypassed. Does not supervise
anything and does not get assigned a zone response type.
Zone 95: Keypad Emergencyactivated by pressing the keypad [A] key or by
simultaneously pressing the [1] and [*] keys. Keys must be held for
two seconds.
Zone 96: Keypad Emergency – activated by pressing the keypad [C] or by
simultaneously pressing and holding the [3] and [#] keys for 2
seconds.
System zones are programmed through *56 Zone Programming Mode.
The default values for these zones will meet the requirements for most
installations.