Remove 2000 ohm EOL resistor if connected across the zone terminals, and
connect it across the loop wires at the last detector.
3. To supervise power, you MUST use a UL listed End-Of-Line Power
Supervision Relay (i.e. System Sensor No. A77-716B).
18
POWER
TO
DETECTORS
+
-
UL LISTED
COMPATIBLE
CONTROL
PANEL
ZONE
TERMINALS
-
+
-
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
Four-Wire Detector Circuit
2000
EOLR
-
+
4-WIRE SMOKE
DETECTORS
+
-
HEAT
DETECTOR
7
Figure 4: 4-Wire Smoke Detector Connections
COMPATIBLE 4-WIRE SMOKE/COMBUSTION DETECTORS
1412 System Sensor, 4-wire ionization products of combustion
detector
2412 System Sensor, 4-wire photoelectric smoke detector
2412TH System Sensor, 4-wire photoelectric smoke detector
w/135º F (57º C) heat detector
2112/24T System Sensor low-profile 4-wire photoelectric smoke detector
w/135º F (57º C) heat detector
Wiring 2-Wire Smoke Detectors To Zone 5
1. Connect up to 16 of the 2-wire smoke detectors listed below across zone 5
terminals 15 (+) and 16 (–). Observe proper polarity when connecting the
detectors.
2. Connect the EOL resistor at the last detector.
3. See “Programming Hard-Wired Zones” later in this section for a detailed
programming procedure.
Due to the alarm current available on zone 5, only one smoke detector at a
time can be supported in the alarmed state.